Siemens Siemens 3RV2031-4RA10 Motor Protection Circuit Breaker, 690 V AC, 80 A, 4 kA Interrupt, 3 Poles, Thermal Magnetic Trip
Selected SIRIUS_3RV2031_4JA10.jpg

Features
- Minimization of energy losses through optimization of the bimetal trip units
- Reduction of inherent power loss
- Less heating of the control cabinet
- Smaller control cabinet air conditioners can be used
- 3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks)
- 22000 W at 230 VAC, 37000 W at 400 VAC, 55000 W at 500 VAC, 75000 W at 690 VAC
- 65 kA at 240 VAC, 65 kA at 400 VAC, 8 kA at 500 VAC, 4 kA at 690 VAC
- 70 to 80 A thermal overload release, 1040 A instantaneous overcurrent release
- Without auxiliary switch
Description
Siemens Motor Protection Circuit Breaker, 690 V AC, 80 A, 75 kW Power, 50/60 Hz Frequency, 4 kA Interrupt, S2 Frame, Thermal Magnetic Trip, 70 to 80/1040 A Trip, 3 Pole, 3 ph, Screw Connection, 18 to 2 AWG, 18 to 1 AWG Wire, IP00/IP20 Enclosure, DIN Rail/Snap-On/Threaded Mounting, -20 to 60 deg C, 140 mm H x 55 mm W x 149 mm D Dimensions