Mersen Mersen AMP-TRAP® 2000 SmartSpot® A4BQ1000 Current Limiting Low Voltage North American Time Delay Power Fuse, 1000 A, 600 V AC, 200 kA Interrupt, L Class, Cylindrical Body

Selected IDW_IMAGE_ccfb89127f1c269ba6b7caedc332c78c7efa1024b01b780374ad70bcd9fee247.jpg
IDW_IMAGE_ccfb89127f1c269ba6b7caedc332c78c7efa1024b01b780374ad70bcd9fee247.jpg

Features

  • Fastest operation under short circuit conditions - let-thru currents are typically 20% lower, with a corresponding let-thru energy (clearing I2t) up to 40% lower than the next fastest class L fuse
  • Time delay for high inrush loads such as motors and transformers, without nuisance opening
  • 300 kA interrupting rating, self certified (UL witnessed)
  • Most current limiting for lowest peak let-thru current, even at fault currents up to 300 kA
  • Pure silver links ensure lowest let-thru current and longer fuse life
  • Easy 2-to-1 selectivity for prevention of nuisance shutdowns and "blackouts"
  • Rejection style design prevents replacement errors (when used with recommended fuse blocks)
  • High visibility orange label gives instant recognition
  • Reduced inventory because A4BQ can replace all older types of class L fuses now in service
  • Metal embossed date and catalog number for traceability and lasting identification
  • Fiberglass body provides dimensional stability in harsh industrial settings
  • High grade silica filler ensures fast arc quenching
  • Silver plated copper contact

Description

Mersen AMP-TRAP® 2000 SmartSpot® Power Fuse, Current Limiting Low Voltage North American Time Delay, Series: A4BQ, Non-Indicating, Rejection, 1000 A, 600 V AC, 200 kA Interrupt, Class: L, 4 s at 500% Response, Blade Terminal, Bolted-On Mounting, Cylindrical Body, Dual Element, Fiberglass, 2-1/2 in Dia x 10-3/4 in L Body